Product details

In thermal power plant DCS control systems and substation dispatch communication systems, even millisecond power interruptions can trigger major accidents. With 35 years of industry expertise, Santak's power-dedicated UPS SPU series is engineered to address unique power sector demands: its DC bus direct-connection technology integrates directly with the plant's 220V DC panel, eliminating the need for additional battery banks—cutting 50% of maintenance costs while avoiding battery aging risks. During grid flickers, the device instantly switches to DC power, coupled with ultra-precise AC220V±1% stabilized output, ensuring continuous stable operation for critical equipment like DEH electro-hydraulic control systems.Designed for high-dust and strong EMI environments in substations, the SPU series meets DL/T1074-2019 EMC standards, operating continuously at -25°C to 55°C with 95% humidity. Its anti-corrosion coating and seismic structure easily withstand harsh substation conditions. For power system nonlinear load impacts, it features intelligent waveform correction technology, maintaining THD≤3% pure sine wave output even with IT device switching power supplies or motor start/stop distortions.Test data shows the SPU series maintains ≥83% energy conversion efficiency under extreme ±25% grid voltage fluctuations. Combined with overload bypass transfer, short-circuit current limiting, and other multi-protection mechanisms, it ensures 365-day zero-downtime protection for critical power equipment.

Product Parameters

  • Model:Power Specialized UPS SPU 1kVA
  • Rated Capacity:1kVA
  • DC Source (DC220V):Y
  • DC Source (DC110V):Y
  • Input AC Single Phase (1P):Y(1P2W)
  • Input Voltage:220V±25%
  • Input AC Three Phase (3P):Special Specification Support
  • Input Voltage:/
  • Input Frequency:50Hz/60Hz ±10%
  • Input DC Voltage and Range:DC220V (Rated) DC180V~DC270V DC110V (Rated) DC90~DC135V
  • Output Voltage and Accuracy:AC220±1% (1P2W)
  • Output Frequency:50Hz/60Hz ±0.1%
  • Output Waveform Distortion Rate:<3% (Linear Load), <5% (Non-linear Load)
  • Output Overload Capacity:<=100% Continuous Load 100%~120% 10 Minutes Transfer to Bypass 120%~150%, 60 Seconds Transfer to Bypass ≥150%, 1 Second Transfer to Bypass
  • Output Power Factor:0.8
  • Output Crest Factor:0.125694444
  • Output Efficiency:≥83%
  • Protection Function Battery:Battery Low Voltage Auto Shutdown, Circuit Breaker Protection
  • Protection Function Overload Capacity:Transfer to bypass after overload, automatically recover after load reduction
  • Protection Function Short Circuit:Current limit auto shutdown, fuse and circuit breaker protection
  • Protection Function Fault:Fault or internal overtemperature, automatically transfer to bypass and alarm
  • Protection Function Frequency:50Hz/60Hz ±10%
  • Protection Function EMI/EMC:DL/T 1074-2019 BG/T 7260.2-2009
Loading...